HLP-A100 Series
HLP-A100 Series Operating Manual
-
179
-
Field
Description
01
FC address
10
Function
0C 1B
The register address of C03.10 is 310*10-1=3099(0x0C1B)
00 01
Register number
02
Byte number
00 00
The value of 310[2] is 0
69 BB
CRC check
Field
Description
01
FC address
10
Function
0C 1B
The register address of C03.10 is 310*10-1=3099(0x0C1B)
00 01
The number of register
72 9E
CRC check
Exception code
Description
0x00
Parameter number does not exist
0x01
Defined parameters can not be written
0x02
The value exceeds the upper limit of the parameter
0x03
Index does not exist
0x04
The parameter is not array type
0x05
Data type exception
Transmit data 2
Receive data 2
12.10 Exception code
When a communication exception is happened, the inverter returns data
format as following:
Address
Function
Exception code
CRC check
8 bits
8 bits
8 bits
16 bits
Summary of Contents for HLP-A100 Series
Page 1: ......
Page 2: ...HLP A100 Series Operating Manual...
Page 3: ......
Page 7: ...HLP A100 Series Operating Manual HLP A100 Series 6...