Chapter 7 Quick Application Guide
7.1 Motor Parameter Adaption
7.2 Using LCP to control the drive [HAND]
1. Parameter initialization. (C14.22 =2);
2. Resboot the drive;
3. Enter motor nameplate data to C01.20 to C01.25.
4. Choose option [2] of C01.29 to enable AMA.
5. Press “HAND” via LCP or apply start signal via “FOR” terminal in
remote control mode to enable AMA, -AT- will be displayed.
6. Wait for the LCP displays “PUSH ENT”, press “ENTER”key, AMA
complet.
Description: AMA doesn’t need to rotate motor. Measurements are stored in
C01.30, C01.33, and C01.35.
1. Parameter initialization (C14.22=2);
2. Reboot the drive;
3. Frequency source: Use potentiometer to set the f requency for LCP
with pot;
Use UP/DOWN key (
) to set the f requency
for LCP without pot;
4. Press “HAND” key on LCP to start the f requency converter.
5. Press“OFF/RESET”key on LCP to stop the f requency converter;
Note: Control panel potentiometer is used as the only source of the f requency
converter in HAND mode. (For LCP without potentiometer,
use arrow key to set the f requency); Set the lower or upper
potentiometer limit via C06.81 and C06.82.