HLP-A100 Series Operating Manual
HLP-A100 Series
-
110
-
[3] Logic or, Activate via serial communication port or a digital input;
Function: Select control of Set-up Select f unction via digital input or bus.
C08.56
Function Description
Range
Unit
Default Setting
Preset Reference Select
0~3
3
Option: [0] Digital input, Aciviate via a digital input;
[1] Bus, Activate via serial communication port;
[2] Logic and, Activate via serial communication port and a digital
input;
[3] Logic or, Activate via serial communication port or a digital input;
Function: Select control of Preset Reference Select f unction via digital input
or bus.
C08.94 Function Description
Range
Unit
Default Setting
Bus Feedback 1
-32768~32767
0
Function: Enter the value to be used as bus-feedback. Hex-value 4000H
corresponds to 100% feedback/range is +/-200%.
C08.9* Bus Jog/Feedback
C13.00 Function Description
Range
Unit
Default Setting
Sample PLC Mode
0~2
0
Option: [0] *Disabled;
C13.0* Simple PLC Settings
6.10 Parameter Group 13: Simple PLC
Simple PLC is a user-def ined sequence of operation (C13.52[x]). When
the associated user-defined envents (C13.51[x]) is set to true, Sample PLC will
perform these operations.
Events and related operations are paired, that is , once an event is “true”,
will execute its associated action. You can set up to 30 events and operations.
Start and stop simple PLC: Selected by C13.00 order or parallel control,
when start event (par.13.01) is “true”, start simple PLC, when stop event (C13.02)
is “true”, Simple PLC will be stopped. In addition, you can also choose off [0]
(C13.00) to stop the simple PLC.
Attention: Simple PLC f unction is only valid in auto mode.
Use the Sample PLC settings to active
、
disable or reset simple PLC.