HLP-A100 Series
HLP-A100 Series Operating Manual
-
85
-
C04.6* Speed Bypass
C04.61
Function Description
Range
Unit
Default Setting
Bypass Speed From
0.0~400.0
Hz
0.0
Array: [3]
Function: This parameter is a dyadic Array, [0] is used to set the bypass speed
f rom of bypass speed range 1, [1] is used to set the bypass speed
f rom of bypass speed range 2,and [2] is used to set that of bypass
speed range3.
Description of Choice: Some systems call for avoiding some certain output
speed due to resonance problems in system. The drive will pass
quickly when it approaching to the Bypass Speed area.
C04.63
Function Description
Range
Unit
Default Setting
Bypass Speed to
0.0~400.0
Hz
0.0
Array: [3];
Function: This parameter is a dyadic array, [0] is used to set the bypass speed
to of bypass speed range 1, [1] is used to set the bypass speed to of
bypass speed range 2,and [2] is set as that of bypass speed range3.
may be disabled for special purpose (e.g. small motor running pure
U/f mode). However, choosing [0] Off, f unction disabled, may lead to
overheating, Holip strongly recommends to make an active setting to
avoid motor damage.