HLP-A100 Series
HLP-A100 Series Operating Manual
-
7
-
2.3 Technical Specifications
Item
Specif ication
Power
supply
Supply voltage
three phase 380-480V -20%-+10%;
Frequency
48-62Hz;
Max. imbalance
3%;
Motor
output
Output voltage
three phase 0-100% of supply
voltage;
Output f requency
V/F : 0-400Hz , VVC+: 0-200Hz;
Main
control
f unctions
Control mode
V/F, VVC+;
Start torque
1Hz 150%;
Overload capacity
150% rated output current (60s),
200% rated output current(1s);
PWM switch
f requency
2K-16KHz;
Speed setting
resolution
Digital: 0.001Hz; analogy: 0.5‰ of the
max. operating f requency ;
Speed open-loop
control accuracy
30 - 4000 rpm: tolerance±8 rpm;
Speed closed-loop
control accuracy
0 - 6000 rpm: tolerance±0.15 rpm;
Control command
source
LCP , digital terminal, local bus;
Frequency setting
source
LCP , analog, pulse, local bus;
Ramp control
Selectable 4-speed steps ramp up and
down times 0.05-3600.00s;
Basic
Functions
AMA Function; Motor Magnetisation; Slip Compensation;
Torque compensation; Automatic Voltage Regulation; V/
F Control, DC Brake; AC brake; Speed Limit; Current
Limit; Flying Start; Reset Function; Counter; Timer; PI
Controller.
Application
Functions
Speed Open-loop Control; Process Closed-loop Control;
Wobble Function; Cascade controller; Winder; Jogging
; Multi-speed Control via Digital input; Multi-speed
Control via Reference; SLC ( including Order Control
、
Parallel Control ) ; Mechanical Braking;UP/DOWN;Catch
up /Slow down; Relative Scaling Reference etc.