HLP-A100 Series
HLP-A100 Series Operating Manual
-
75
-
C03.13 Function Description
Range
Unit
Default Setting
Speed Up/Down Value
0.01~50.00 Hz
0.10
Function: Enter the Speed Up/Down value.
to the actual reference constituting new setting at which the
frequency converter is going to run, calculated as follows:
Total reference= reference ±reference × (Catch up/Slowdown
value)
If this function is inactive, the reference returns to its original value (the
actual reference).
For example: Set C05.12=28, C05.13=29, C03.12=30, assuming the
actual reference value is 20 Hz, when only DI1 is on, the output
frequency is 26 Hz, when only DI2 is connected, the output
frequency is14Hz, when both DI1 and DI2 are on, the output
frequency is 20Hz.
C03.14 Function Description
Range
Unit
Default Setting
Preset Relative
Reference
-100.00~100.00 %
0.00
Function: Define an adjustable Preset Relative Reference which is to be
added to the total reference as a percentage value of the actual
reference .
Total Reference=Actual ReActual Reference * Preset Relative
Ref Actual reference * Relative Scaling Reference
Example:
Min
Reference/
C03.02
Preset
Relative
Reference/
C03.14
Relative
Scaling
Reference
VI/C03.18=1
Preset
Reference/
C03.10
Max
Reference/
C03.03
Output
Frequency
(Hz)
0
0%
10V
20%
50
10+0+10=20
0
10%
8V
20%
50
10+1+8=19
0
20%
5V
20%
50
10+2+5=17
0
30%
3V
20%
50
10+3+3=16
0
40%
0V
20%
50
10+4+0=14