13
-
Installation dimensions of the inverter:
Details of terminal tightening torques:
3.3 Installation and Wiring
3.3.1 Electrical Installation in General
Caution
● All cabling must comply with national and local regulations on
cable cross-sections and ambient temperature. Copper conductors
required.
Power (KW) and Voltage
levels
Torque (Nm)
1×200-
240V
3×200-
240V
3×380-
480V Line Motor
DC connection/
Brake
Control
terminals Relay
11-22
1.2
1.2
1.2
0.15-0.4
0.4
30-75
8
8
8
0.15-0.4
0.4
90-220
16
16
16
0.15-0.4
0.4
Item
Dimension(mm)
A(mm)
B(mm)
C(mm)
D(mm)
E(mm)
F(mm)
G(mm)
A3
148
192
340
365
189
6.5
-
A4
150
214
395
420
194
6.5
-
A5
250
292
530
563
216.5
10
200
A6
280
330
680
720
308
10.5
215
A7
220
350
765
799
375
10.5
280
A8
345
486
863
900
390
10.5
410
3.3.2 Fuse and Main Circuit Terminals Specifications
Model
Fuse(Rated current/A) Main Circuit Terminals
HLP-A100001143
63
M4
HLP-A100001543
80
M4
HLP-A10018D543
80
M5
HLP-A100002243
100
M5
HLP-A100003043
100
M8