Function Description
Range
Unit
Default Setting
Pump Type Selection
0~1
0
Option: [0] Feed pump;
[1] Draining pump;
Function: There are two kinds of water level control, one is used for feed
pump, and the other is used for draining pump. the set point equals
to normal set point setting when the water level between “low
water level” and “high water level”; the set point equals to “standby
pressure 2” when the water level between “scarcity water level”
and “low water level”; the set point equals to “standby pressure
1” when the water level between “high water level” and “overrun
water level”; the “overrun water level warning” happens when the
water level above the “overrun water level”, and the lead pump will
be stopped and all lag pumps will be destaged. The “overrun water
level warning” will be recovered when the water level below the
“low water level” and the cascade controller will be restated.
When draining pump is used, the set point equals to normal set
point setting when the water level between “low water level” and
“high water level”; the set point equals to “standby pressure 1”
when the water level between “scarcity water level” and “low water
level”; the set point equals to “standby pressure 2” when the water
level between “high water level” and “overrun water level”; the”
scarcity water level warning” happens when the water level below
the “scarcity water level”, and the lead pump will be stopped and all
lag pumps will be destaged. The “scarcity water level warning” will
be recovered when the water level above the “high water level” and
the cascade controller will be restated
C25.61
Function Description
Range
Unit
Default Setting
Water Level Signal Source
0~8
0
Option: [0]: Digital input;
[1]: VI;
[2]: AI;
[8]: Pulse input;
Function: Define the source of the water level signal.
C25.6* Water Level Control