HLP-A100 Series
HLP-A100 Series Operating Manual
-
143
-
C25.62
Function Description
Range
Unit
Default Setting
Scarcity Water Level
0~100
%
0
Function: Set the scarcity water level, the setting rang is f rom 0 to low water
level. 100% corresponding to the pool water level at10V voltage.
C25.63
Function Description
Range
Unit
Default Setting
Low Water Level
0~100
%
0
Function: Set the low water level, the setting rang is f rom the scarcity water
level to low water level. 100% corresponding to the water level at
10V voltage.
C25.64
Function Description
Range
Unit
Default Setting
High Warter Level
0~100
%
0
Function: Set the high water level, the setting rang is f rom low water level
to high water level. 100% corresponding to the water level at 10V
voltage.
C25.65
Function Description
Range
Unit
Default Setting
Overrun Water Level
0~100
%
0
Function: Set the overrun water level, the setting rang is f rom 0 to 100%,
100% corresponding to the water level at 10V voltage.
C25.66
Function Description
Range
Unit
Default Setting
Standby Pressure 1
0.000~99.999
kg
3.000
Function: To prevent the outlet pipe speed faster than the inlet pipe, leaving
the water level rose too quickly into the pool, and even form over-
voltage condition, so the pressure 1 is an alternative requirement to
run.
C25.67
Function Description
Range
Unit
Default Setting
Standby Pressure 2
0.000~99.999
kg
7.000
Function: To prevent the velocity of the inlet pipe is less than the outlet pipe,
leaving the pool water level decreases too fast, and even form
under-voltage condition, pressure 2 is an reserved requirement to
run.