HLP-A100 Series
HLP-A100 Series Operating Manual
-
81
-
Description of Choice: Quick Stop Ramp Down Time is applicable when
Quick Stop Ramp Time is activated, see C05.1*, choose [4].
6.5 Parameter Group 04: Limits/warnings
C04.1* Motor Limits
*C04.10 Function Description
Range
Unit
Default Setting
Motor Speed Direction
0~2
2
Option: [0] Clockwise, the motor shaft rotates in clockwise direction; this
setting prevents the motor from running in counter clockwise
direction.
[1] Counter clockwise, motor shaft rotates in counter clockwise
direction, this setting prevents the motor from running in
clockwise direction.
[2] Both Directions, with this setting, the motor can run in both
directions.
*C04.12 Function Description
Range
Unit
Default Setting
Motor Speed Low Limit 0.0~400.0
Hz
0.0
Function: Set the minimum limit for Motor Speed, the motor speed low
limit can be set to correspond to the minimum output frequency
of the motor shaft . The motor speed low limit must not exceed
the Motor Speed High Limit in C04.14.
*C04.14 Function Description
Range
Unit
Default Setting
Motor Speed High Limit 0.0~400.0
Hz
65.0
Function: Enter the maximum limit for Motor Speed , the motor
speed high limit can be set to correspond to the maximum
manufacture’s rated motor speed. The motor speed high limit
must exceed the Motor Speed Low Limit in C04.19.
C04.18 Function Description
Range
Unit
Default Setting
Current Limit
0~300
%
150
Function: Set the output current high limit.
Attention: If a setting in C01.20 to C01.25 is changed, this parameter is
not automatically reset to default setting.