HLP-A100 Series
HLP-A100 Series Operating Manual
-
55
-
*C00.06
Function Description
Range
Unit
Default Setting
Grid Type
0~132
*
Option: [0] 200-240V/50Hz/IT-Grid;
[1] 200-240V/50Hz/IT-Delta;
[2] 200-240V/50Hz;
[10] 380-440V/50Hz/IT-Grid;
[11] 380-440V/50Hz/IT-Delta;
[12] 380-440V/50Hz;
[20] 440-480V/50Hz/IT-Grid;
[21] 440-480V/50Hz/IT-Delta;
[22] 440-480V/50Hz;
[30] 525-600V/50Hz/IT-Grid;
[31] 525-600V/50Hz/IT-Delta;
[32] 525-600V/50Hz;
[100] 200-240V/60Hz/IT-Grid;
[101] 200-240V/60Hz/IT-Delta;
[102] 200-240V/60Hz;
[110] 380-440V/60Hz/IT-Grid;
[111] 380-440V/60Hz/IT-Delta;
[112] 380-440V/60Hz;
[120] 440-480V/60Hz/IT-Grid;
[121] 440-480V/60Hz/IT-Delta;
[122] 440-480V/60Hz;
[130] 525-600V/60Hz/IT-Grid;
[131] 525-600V/60Hz/IT-Delta;
[132] 525-600V/60Hz;
Function:A correct type of Grid can optimize the output voltage/
frequency.
C00.10 Function Description
Range
Unit
Default Setting
Active Set-up
1~9
1
Option: [1] Set-up 1;
[2] Set –up 2;
[9] Multi set-up;
Description of choice: HLP-B series inverter contains 2 set-ups: set-up1
and set-up 2, which can be switched via digital inputs or serial
communication commands. Binary code of the digital input
terminals correspond with set-ups as follows: