HLP-A100 Series
HLP-A100 Series Operating Manual
-
139
-
C25.33 Function Description
Range
Unit
Default Setting
Recovery Low Pressure
0.0~3600.0
S
10.0
Function: This parameter used together with “Recovery Low Pressure Level”
(C25.32).
C25.34 Function Description
Range
Unit
Default Setting
Over Pressure Warning
Level
0.000~99.999 kg
7.000
Function: This parameter used to define over-pressure warning level, when
the actual pressure is less than “Over-pressure Warning Level”,
and lasts more than “Over Pressure Warning Delay Time”, then, an
Over Pressure Warning occurs, multi-f unction conjunction acts,
the drive stops.
C25.35 Function Description
Range
Unit
Default Setting
Over Pressure Warning
Delay Time
0.0~3600.0
s
10.0
Function: This parameter should be used together with “Over Pressure
Warning Level”.
C25.36
Function Description
Range
Unit
Default Setting
Recovery High
Pressure Level
0.000~99.999 kg
5.000
Function: When actual pressure rise above” Recovery High Pressure Level”,
and it lasts longer than “Recovery High Pressure Delay Time”, then,
over pressure warning is cancelled, the inverter starts to run.
C25.37
Function Description
Range
Unit
Default Setting
Recovery High
Pressure Delay Time
0.0~3600.0
s
10.0
Function: This parameter used in conjunction with “Recovery High Pressure
Level”.