HLP-A100 Series
HLP-A100 Series Operating Manual
-
89
-
Array: [0]-[1] Array[0] indicates relay1, array[1] indicates relay2.
Option: [0] No operation;
[1] Control ready, inverter control card have received supply voltage;
[2] Drive ready, Frequency converter is ready for operation and
applies supply signal on control card;
[3] Drive ready, remote, Frequency converter is ready for operation
and is in Auto-on mode;
[4] Enable/No warning, Frequency converter is ready for operation.
No start or stop command is given. No warning is present;
[5] Drive running, Motor is running;
[6] Running/No warning, Motor runs and no warnings are present;
[7] Run in range/No warning. Motor runs within programmed
current ranges, see C04.50 and C04.51. No warnings are present;
[8] Run on reference/No warning. Inverter runs at reference speed
without warnings;
[9] Alarm. Frequency converter alarms;
[10] Alarm or warning. An alarm or warning occurs;
[12] Out of current range. Output current exceeds the current range
set in C04.50 and C04.51;
[13] Below current, low. Output current is lower than set in C04.50;
[14] Above current, high. Output current is higher than set in C04.51;
[15] Beyond f requency range. Output f requency beyond range set in
C04.52 and C04.53;
[16] Below f requency, low. Output f requency is lower than value set
in C04.52;
[17] Above f requency,high. Output f requency is higher than value set
in C04.53;
[18] Beyond the scope of the feedback. The feedback received f rom
the inverter exceeds the setting range in C04.56 and C04.57;
[19] Below feedback,low. The feedback received f rom inverter is
lower than settings in C04.56;
[20] Above feedback, high. The feedback received f rom inverter is
higher than settings in C04.57;
[21] Thermal warning. A thermal warning occurs;
[22] Ready, no Thermal warning. Frequency converter is ready for
operation and no over-temperature warning is present;
[23] Remote ready, no Thermal Warning. Frequency converter is
ready for operation in remote control, and no over-temperature
warning is present;
[24] Ready-Voltage OK. Frequency converter is ready for operation,
main voltage is within specified voltage range;
[25] Reverse. Motor runs in counter clockwise;