HLP-A100 Series Operating Manual
HLP-A100 Series
-
10
-
Item
Specif ication
Environment
Enclosure
IP20;
Ambient
temperature
-10
℃
- 40
℃
;
Humidity
5%-85% ( 95% without condensation);
Vibration test
≤75KW:1.14g;90-220KW:0.7g;
Max. altitude above
sea level
1000m, derating use when more than
1000 meters;
Motor cable length
Shield cable: 50 meters, unshield
cable: 100 meters;
Others
DC Choke
≥30kW with DC choke;
Brake Unit
≤22KW with Brake Unit;
Attention: Inverter under special environment (derating
)
:
● Derating for ambient temperature: If the f requency converter is
operated over 40
℃
ambient temperature, the continuous output
current should be decreased. The f requency converter has been
designed for operation at max 50
℃
ambient temperation with one
motor size smaller than normal. Continuous operation at f ull load at
50
℃
ambient temperation will reduce the lifetime of the f requency
converter.
● Derating for low air pressure: The cooling capability of air is
decreased at low air pressure. Below 1000m altitude no de-rating is
necessary but above 1000m the ambient temperature or the maximum
output current should be decreased. Dcrease the output by 1% per
100m altitude above 1000m or reduce the max. ambient temperature
by 1 degree per 200m.