HLP-A100 Series Operating Manual
HLP-A100 Series
-
114
-
C13.12 Function Description
Range
Unit
Default Setting
Comparator Value
-9999.0~9999.0
0.0
C13.20 Function Description
Range
Unit
Default Setting
Simple PLC Timer
0.00~3600.00
s
0.00
Array: [8];
Function: Enter the value to define the duration of the FALSE output f rom
the programmed timer. A timer is only TRUE if it is started by an
action and till the timer value has exceeded the set time.
C13.2* Timers
Use the timer output to define an event (see C13.51) or acts as Boolean
inputs of the logic rules (see C13.40
、
C13.42 or C13.44).
C13.40 Function Description
Range
Unit
Default Setting
Logic Rule Boolean 1
0~64
0
Array: [4];
Option: Please refer to C13.01;
Function: Select the first boolean(true or false) input for the selected logic
rule.
C13.41 Function Description
Range
Unit
Default Setting
Logic Rule Operator 1
0~8
0
Array: [4] ;
Option: [0] Disabled, ignoring C13.40 and C13.42 ;
[1] And, evaluates the expression [C13.40] AND [C13.42];
[2] Or, evaluates the expression [C13.40] OR [C13.42];
C13.4* Logic Rules
Combine up to three boolean inputs (TRUEor FALSE inputs) f rom
timers
、
comparators
、
digital inputs
、
status bits and events using the logical
operators AND
、
OR and NOT. C13.40
、
C13.42 and C13.44 are used to select
logic rule Booleans, and C13.41
、
C13.43 is for selecting logic rule operators.
Caculation order: First, select three Boolean inputs f rom C13.40
、
C13.41
and C13.42 for the selected logic rule, and then the result (“TRUE or FALSE”)
as a logic boolean value, together with other two boolean inputs got f rom
C13.43 and C13.44 to obtain the f inal result of the calculation (“TRUE or
FALSE”).