HLP-A100 Series
HLP-A100 Series Operating Manual
-
119
-
C14.12 Function Description
Range
Unit
Default Setting
Function at Mains Imbanlance 0~3
0
C14.16
Function Description
Range
Unit
Default Setting
Low Voltage Mode
0~1
0
Option: [0] Trip, f requency converter trips;
[1] Warning, f requency converter issues a warning (but continues to
run);
[2] Disabled, no action is taken;
Function: Select actions when a severe mains imbalance is detected.
Option: [0] Disable;
[1] Enable;
Function: When the power input voltage is low, enable low voltage mode can
improve load capacity. When the voltage is 15% lower, enable low
voltage mode can make the inverter long-term f ull load; When
the voltage is 20% lower, the inverter needs to drop load work;
When the voltage is normal, do not enable the low voltage mode,
otherwise it will reduce the machine usef ul life.
C14.1* Mains On/Off
C14.21 Function Description
Range
Unit
Default Setting
Automatic Restart Time
0~600
s
10
C14.20 Function Description
Range
Unit
Default Setting
Reset Mode
0~13
0
Option: [0] Manual reset, perform reset via [reset]-button or digital inputs;
[1] - [10] Auto reset 1-10, can perform 1-10 automatic resets af ter trips;
[11] Auto reset11, can perform 15 automatic resets af ter trips;
[12] Auto reset12, can perform 20 automatic resets af ter trips;
[13] Infinite auto reset, can perform an infinite number of automatic
resets af ter tripping;
Function: Select reset f unction af ter tripping. Once auto reset is selected, the
f requency converter will be restarted af ter an alarm. If reset have
been done and the running signal is active, f requency converter
will restart automatically.
Attention: If the auto reset mode is selected, the f requency converter may
possibly restart automatically af ter the alarm disappear.
C14.2* Trip Reset