HLP-A100 Series
HLP-A100 Series Operating Manual
-
17
-
Description of I/O control terminals:
Symbol
Description
Specification
VDD
24Vpower
supply
Max.load 200mA, with over load and
short circuit protection f unctions;
+10V
10V power
supply
Max.load 10 mA, with over load and
short circuit protection f unctions;
Digital input
(FOR
、
REV
、
DI1
、
DI2
、
DI3
、
DI4)
Digital control
terminals
1
、
Logic:
PNP <DC5V logic ‘0’;
>DC10V logic ‘1’;
NPN >DC19V logic ‘0’;
<DC14V logic ‘1’;
2
、
Voltage: DC 0-24V;
3
、
Input resistance: 5KΩ;
4
、
Input voltage rang: max ±28V;
5
、
Switch PNP and NPN model by
Jumper switch.
Analog input
(VI
、
AI)
Analog setting/
Feedback
Set by the related parameter, analog input
channel can be configurated to 0-20mA
or 0-10V:
Voltage input:
1
、
Input impedance: about 10 KΩ;
2
、
Maximum withstand voltage is 20V,
duration of 2 seconds, the maximum
reverse
voltage is -15V , duration of 2seconds.
Current input:
1
、
Input impedence≤500Ω;
2
、
Maximum withstand current is 29
mA duration of 2 seconds.
Analog
、
communication
(GND)
Analog
、
communication
ground
Isolated f rom internal digital
ground(COM)
Pulse input DI4 Pulse setting/
Feedback
1
、
Pulse input: 0.001-100.000KHz;
2
、
Voltage range: 24V ± 20%;
3
、
Input duty ratio: 40%-60%;