HLP-A100 Series Operating Manual
HLP-A100 Series
-
144
-
C25.69
Function Description
Range
Unit
Default Setting
Water Level DI Delay
Time
0~3600.0
s
20.0
C25.68
Function Description
Range
Unit
Default Setting
Water Level Dead Band
0~100
%
5
Function: When the “water level signal source” selects “Analog input” or
“Pulse Input”, this parameter is used to prevent set point switch
between normal set point and standby pressure too f requently. The
deadband must be exit in “low water level” and “high water level”.
When water level rises, the actual water level higher than water
level(upper level, lower level etc.) plus the water level deadband,
switch the running pressure; when the water level falls, the actual
water level drops below the set level(upper level, lower level etc.)
minus the water level deadband, switch the operating pressure.
Function: When “water level signal source” selects “Digital input”, this
parameter is used to prevent set point switch between normal set
point and standby pressure too f requently . The set point switches
when switch signal lasts water level DI delay time.
C25.80 Function Description
Range
Unit
Default Setting
Alarm Handl Selection
0~3
0
Option: [0]: Stop all;
[1]: Lag pump 1 Running;
[2]: Lag pump 2 Running;
[3]: Lag pump 1
、
2 Running;
Function: Set action of the auxiliary pump when drive fault occurs.
C25.8* Fault Handle