HLP-A100 Series Operating Manual
HLP-A100 Series
-
54
-
Chapter 6 Parameter Description
6.1 Parameter Group 00: Operation/Display
C00.0* Basic Settings
*C00.03 Function Description Range
Unit
Default Setting
Regional Settings
0~1
1
Option: [0] 50Hz, Motor frequency default value is 50 Hz, see C01.23;
[1] 60Hz, Motor frequency default value is 60 Hz, see C01.23;
Function: This parameter is used to select motor frequency default value
according to different regions;
Attention: This parameter can not be adjusted when motor is running. At
the same time changing this parameter may result in changes in
the value of the following parameters: C01.23
、
C01.25
、
C01.39
、
C01.56
、
C01.30
、
C01.33
、
C01.35.
C00.04 Functon Description
Range
Unit
Default Setting
Operation State at
Power-up(Hand)
0~2
1
Option: [0] Resume, local reference is stored and used after power up;
[1] Forced stop, ref=old, local reference is stored and used after
power up;
[2] Forced stop, ref=0, local reference is set to 0;
Function: This parameter is used to control whether or not the frequency
converter should automatic running the motor when powering
up after a power down in Hand mode.
Description of choice: When select “[0]”, frequency converter starts
in same Hand mode roof state as when powered off; When
select“[1]”, frequency converter powers up in off state meaning
that motor is stopped after power up; When select“[2]”,
frequency converter powers up in off state meaning that motor
is stopped after power up. Local reference is set to 0. Thus motor
will not start running before local reference has been increased.
Attention: If LCP with potentiometer is mounted, reference is set
according to actual potentiometer value.