HLP-A100 Series
HLP-A100 Series Operating Manual
-
67
-
C01.8* Stop Adjustments
C01.80 Function Description
Range
Unit
Default Setting
Function at Stop
0~1
0
Option: [0] Coast, the inverter is off;
[1] DC Hold, the motor is energized with a DC current. See par.
C02.00 DC Hold Current for more information.
Function: Here it is possible to select the stop function according to
different applications.
*C01.73
Function Description
Range
Unit
Default Setting
Flying Start
0~1
0
Option: [0] Disabled;
[1] Enabled;
Description of Choice: This function applies for the inertia load to restart
due to mains drop-out; If Clockwise[0] is selected(C04.10),
and no rotating motor is found, It is possible to use DC-brake
command to ramp down the motor speed to 0 rpm, and then start
the motor in the normal way; If Both directions [2](C04.10) is
selected, and no rotating motor is found, the drive will assume
the motor is stationary or in low-speed rotation, and then start
the motor in the normal way. When Flying start is enabled,
C01.71 (Start delay) and C01.72 (Start function) is invalid.
Warning: This function is not suitable for hoisting applications.