HLP-A100 Series
HLP-A100 Series Operating Manual
-
113
-
C13.10 Function Description
Range
Unit
Default Setting
Comparator Operand
0~31
0
Array: [4] ;
Option: [0] Disabled;
[1] Reference [Hz] ;
[2] Feedback [%], feedback signal (0-10V) or (0/4-20mA) corresponds
to -200% ~ 200%;
[3] Motor speed [Hz] ;
[4] Motor current [A] ;
[6] Motor power [kW] ;
[7]Motor Voltage [V];
[12] Analog in VI [%], 100% corresponds to 10V/20mA (depending on
your choice is current input or voltage input);
[13] Analog in AI [%], 100% corresponds to 10v/20mA (depending on
your choice is current input or voltage input);
[20] Alarm number;
[30] Counter A;
[31] Counter B;
For example: Motor current is 25A, C13.10 [0] =4, C13.12 [0] =23, C13.11 [0] =2,
then the output of comparator 0 is true.
C13.11 Function Description
Range
Unit
Default Setting
Comparator Operator
0~2
1
Array: [4] ;
Option: [0] Less than, if the variable selected in C13.10 is less than the set value
in C13.12, the comparator output is true, or, false;
[1] Approx. Equal, if the variable selected in C13.10 equals the set value
in parC13.12, the comparator output is true;
[2] Greater than, opposite with option [0];
Function: Select the operator to be used in the comparison.
C13.1* Comparators
Comparators are used for comparing continuous variables (e.g. output
f requency
、
output current
、
analog input etc.) with f ixed preset values. In
addition, there are some constant value in conjunction with the preset value
for comparison, please refer to options in C13.10. In each of the scanning
integral the comparator will be evaluated once. And directly use the results (true
or false). Parameters in this group are all array-type parameter with index 0-4 .
Select 0 to programme Comparator 0, select index 1 to programme Comparator
1, and so on.