Function: Enter VI High Ref./Feedb. Corresponding to max voltage or max
current set in C06.11 or C06.13.
C06.15
Function Description
Range
Unit
Default
Setting
Terminal VI High
Ref. /Feedb.
-4999.000~4999.000
50.000
C06.16
Function Description
Range
Unit
Default Setting
Terminal Filter Time
Constant
0.01~10.00
s
0.01
Function: Enter the time constant, this is a first-order digital low pass filter
time constant for suppressing electrical noise in analog input VI. A
high time constant value improves dampening but also increases
the time delay through the filter. This parameter can’t be adjusted
while the motor is running.
C06.18
Function Description
Range
Unit
Default Setting
Terminal VI Zero
Dead Band
0.00~20.00 V/mA
0.00
Function: Set the dead-band of VI at 0 speed. When analog input VI ref.
low and ref. high have opposite signs, there must be a set point that
corresponding to an analogue value equals 0. In order to prevent
the set point jitter at zero point due to analog interference, this
parameter should be set properly.