C25.52 Function Description
Range
Unit
Default Setting
Sleep Pressure Delay
0.0~300.0
s
20.0
Function: Def ine the sleep pressure duration before the main pump enter
sleep mode.
C25.53 Function Description
Range
Unit
Default Setting
Sleep Frequency
0.000~400.000 Hz
20.000
Function: Define the low f requency before the main pump go to sleep mode.
C25.57
Function Description
Range
Unit
Default Setting
Awake Level
0.0~150.0
%
80.0
Function: Set the pressure level f rom sleep mode to awake mode. Awake
pressure=Set point*Sleep mode awake level.
C25.54 Function Description
Range
Unit
Default Setting
Sleep Frequency Delay
Time
0.0~300.0
s
20.0
Function: Set the sleep f requency duration before the main pump go to sleep
mode.