HLP-A100 Series Operating Manual
HLP-A100 Series
-
44
-
Item Parameter
No.
Function
Description
Setting range
Unit
Default
setting
Page
No.
Pa
ram
ete
r G
rou
p 1
3: S
im
ple
PL
C
C13.40 Logic Rule
Boolean 1
0~64
0.0
114
C13.41 Logic Rule
Operator 1
0~8
0
114
C13.42 Logic Rule
Boolean 2
Same to C13.40
0
115
C13.43 Logic Rule
Operator 2
0~8
0
115
C13.44 Logic Rule
Boolean 3
Same to C13.40
0
116
C13.51 SL Controller
Event
Same to C13.40
0
116
C13.52 SL Controller
Action
0~69
0
116
Pa
ram
ete
r G
rou
p 14
: S
pec
ial
Fu
nc
tio
ns
C14.01 Switching
Frequency
2~6: 2kHz~6kHz;
7: 8kHz; 8: 10 kHz;
9: 12kHz; 10: 16kHz;
4
118
*C14.03 Over
modulation
0: Off; 1: On;
1
118
C14.08 Damping
Gain Factor
0~200
%
96
118
C14.12
Function
at Mains
Imbalance
0: Trip; 1: Warning;
2: Disabled;
0
119
C14.16
Low Voltage
Mode
0: Disabled; 1:
Enable;
0
C14.20 Reset Mode
0: Manual reset; 1~10:
Automatic reset x
1~10; 11: Automatic
reset x 15;
12: Automatic reset x
20;
13: Infinite auto reset;
0
119
C14.21 Automatic
Restart Time
0~600
s
10
119
C14.22 Operation
Mode
0: Normal Operation;
2: Initialisation;
3: Backup user
settings;4: Recover
user settings;
0
119