134
SuperTrak™ GEN3 System Operation and Maintenance Manual
Rev. 9 (12-2021)
Operating Procedures
Measure the Resistance Between the Ground (Frame)
and the Common Connection
1. Test the resistance as shown below:
2. Look at the value displayed on the multimeter screen and determine if the
resistance is acceptable:
•
Pass - The value is <1
Ω
.
•
Fail - The value is >1
Ω
.
3. Verify that the bonding jumper is correctly installed in the
180 deg. section that contains the control panel electrical interconnect.