Appendix K: Additional PX Information
655
Assumption:
Upper Warning threshold is enabled.
Upper Warning = 20 (degrees Celsius)
Deassertion Hysteresis = 3 (degrees Celsius)
"Deassertion" level = 20-3 = 17 (degrees Celsius)
When the PX detects that a temperature sensor's reading drops below
20 degrees Celsius, moving from the "above upper warning" range to the
"normal" range, either of the following may occur:
If the temperature falls between 20 and 17 degrees Celsius, the PX
does NOT turn on the "deassertion" action.
If the temperature drops to 17 degrees Celsius or lower, the PX turns
on the "deassertion" action to announce the end of the "above upper
warning" state.
Ways to Probe Existing User Profiles
This section indicates available ways to query existing user accounts on
the PX.
With SNMP v3 activated, you get the "user unknown" error when the
user name used to authenticate does not exist.
Any user with the permission to view event rules can query all local
existing users via JSON RPC.
Any user with the permission to view the event log may get
information about existing users from the log entries.
Any authenticated users can query currently-existing connection
sessions, including Webcam-Live-Preview sessions, which show a
list of associated user names.
Содержание PX3-4000 series
Страница 5: ......
Страница 350: ...Chapter 6 Using the Web Interface 329 10 To print the currently selected topic click the Print this page icon...
Страница 615: ...Appendix H LDAP Configuration Illustration 594 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Страница 628: ...Appendix I RADIUS Configuration Illustration 607 10 Select Standard to the left of the dialog and then click Add...
Страница 629: ...Appendix I RADIUS Configuration Illustration 608 11 Select Filter Id from the list of attributes and click Add...
Страница 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Страница 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Страница 648: ...Appendix J Integration 627 3 Click OK...
Страница 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...