Chapter 3: Installation and Configuration
28
Tip: You can type "
show
network
wireless
" to display a shortened
version of wireless settings.
11. If all are correct, type
exit
to log out of the PX. If any are incorrect,
repeat Steps 7 to 10 to change network settings.
The IP address configured may take seconds to take effect.
Cascading the PX via USB
Up to eight (8) Raritan devices are supported as part of a daisy chain.
This daisy chain feature permits multiple PX devices to be cascaded
using USB cables, sharing the Ethernet connectivity accordingly.
Different models can be cascaded as long as they are running a
supported firmware.
The first device in the chain is the master device and all the other are
slave devices. All devices in the chain are accessible over the network,
with the bridging or port forwarding cascading mode activated on the
master device. See
Setting the Cascading Mode
(on page 142).
Only the master device is connected to the LAN. The LAN connection
method varies based on the cascading mode.
The bridging mode supports the
wired
networking only.
The port forwarding mode supports both the
wired
and
wireless
networking.
For more information on the USB-cascading configuration, see the
USB-Cascading Solution Guide
, which is available from Raritan
website's
PX2 Support Files page
(
https://www.raritan.com/support/product/px2/px2-support-files
).
To cascade the PX devices via USB:
1. Verify that the PDUs to be cascaded are running the following
firmware versions by choosing Maintenance > Device Information in
the web interface or using the "
show pdu
" command in the command
line interface. If not, upgrade these devices. See
Updating the PX
Firmware
(on page 324).
PX2 series: version 2.3.1 or later
PX3 series: version 2.5.10 or later
Note: Port forwarding mode over wireless LAN is supported as of
release 3.1.0. You must upgrade all devices in the chain to version
3.1.0 or later if wireless networking is preferred.
2. Select one of the devices as the master device.
Содержание PX3-4000 series
Страница 5: ......
Страница 350: ...Chapter 6 Using the Web Interface 329 10 To print the currently selected topic click the Print this page icon...
Страница 615: ...Appendix H LDAP Configuration Illustration 594 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Страница 628: ...Appendix I RADIUS Configuration Illustration 607 10 Select Standard to the left of the dialog and then click Add...
Страница 629: ...Appendix I RADIUS Configuration Illustration 608 11 Select Filter Id from the list of attributes and click Add...
Страница 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Страница 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Страница 648: ...Appendix J Integration 627 3 Click OK...
Страница 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...