Appendix G: PX Models with Residual Current Monitoring
574
IEC 62020 specification
PX with RCM characteristics
Ability to directly
discriminate
Directionally non-discriminating.
Rated residual operating
current
0.5A (highest value).
Residual currents with
direct current components
Type A.
RCM Self-Test
PX with RCM have a built-in self-test feature that performs these
functions:
When residual current is less than 3mA, 15mA is momentarily added
to determine whether the low reading is due to a faulty sensor. The
residual current added is done in a safe manner which does not run
current into ground or pose operator risk.
The RCM state sensor changes to SELF-TEST and then back to its
original state if self-test passes, or to the FAILURE state if self-test
fails. These state changes are useful to verify your monitoring
systems (SNMP, syslog, or email) are correctly set up to receive PX
event notifications.
Note: If self-test fails, the FAILURE state persists until another self-test
runs and passes.
Web Interface Operations for RCM
The RCM is a PX inlet sensor. To view, configure or run self-test, click
the Inlet icon in the PX Explorer pane.
Checking RCM State and Current
A section titled 'Residual Current Monitor' is available on the Inlet page,
showing both the present RCM state and residual current.
To check RCM state and current on the Inlet page:
1. Click Inlet I1 in the PX Explorer pane, and the Inlet I1 page opens in
the right pane.
2. Locate the Residual Current Monitor section on the Inlet I1 page.
RCM State: There are five states - Normal, Warning, Critical,
Self-test active and Failure. See
RCM State Sensor
(on page
572) for information on these states.
Содержание PX3-4000 series
Страница 5: ......
Страница 350: ...Chapter 6 Using the Web Interface 329 10 To print the currently selected topic click the Print this page icon...
Страница 615: ...Appendix H LDAP Configuration Illustration 594 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Страница 628: ...Appendix I RADIUS Configuration Illustration 607 10 Select Standard to the left of the dialog and then click Add...
Страница 629: ...Appendix I RADIUS Configuration Illustration 608 11 Select Filter Id from the list of attributes and click Add...
Страница 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Страница 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Страница 648: ...Appendix J Integration 627 3 Click OK...
Страница 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...