Chapter 5: Using the PDU
86
Circuit Breakers
PX models rated over 20A (North American) or 16A (international)
contain overcurrent protectors for outlets, which are usually branch
circuit breakers. These circuit breakers automatically trip (disconnect
power) when the current flowing through the circuit breaker exceeds its
rating.
If a circuit breaker switches off power:
A PX3
phase I
model's LCD display shows
CbE
, which means
"circuit breaker error." See
Overcurrent Protector Information
(on
page 561).
A PX3
phase II
model's LCD display shows
open
. To find which
circuit breaker is open (trips), select Alerts or OCPs in the Main
Menu. See
Operating the Dot-Matrix LCD Display
(on page 62).
When a circuit breaker trips, power flow ceases to all outlets connected
to it. You must manually reset the circuit breaker so that affected outlets
can resume normal operation.
Depending on the model you purchased, the circuit breaker may use a
button- or handle-reset mechanism.
Resetting the Button-Type Circuit Breaker
Your button-type circuit breakers may look slightly different from the
images shown in this section, but the reset procedure remains the same.
To reset the button-type breakers:
1. Locate the breaker whose ON button is up, indicating that the
breaker has tripped.
2. Examine your PX and the connected equipment to remove or resolve
the cause that results in the overload or short circuit.
This step is
required, or you cannot proceed with the next step.
3. Press the ON button until it is completely down.
Содержание PX3-4000 series
Страница 5: ......
Страница 350: ...Chapter 6 Using the Web Interface 329 10 To print the currently selected topic click the Print this page icon...
Страница 615: ...Appendix H LDAP Configuration Illustration 594 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Страница 628: ...Appendix I RADIUS Configuration Illustration 607 10 Select Standard to the left of the dialog and then click Add...
Страница 629: ...Appendix I RADIUS Configuration Illustration 608 11 Select Filter Id from the list of attributes and click Add...
Страница 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Страница 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Страница 648: ...Appendix J Integration 627 3 Click OK...
Страница 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...