4-56
Default: [ ]
Pr5.11
Torque setup for emergency stop
Range
Unit
Default
Related
control mode
0 to 500
%
0
P S T F
Note
Set up the torque limit at emergency stop.
When setup value is 0, the torque limit for normal operation is applied.
Pr5.12
Over-load level setup
Range
Unit
Default
Related
control mode
0 to 500
%
0
P S T F
• You can set up the over-load level of effective torque. The overload level becomes 115[%]
by setting up this to 0.
• Use this with 0 setup in normal operation. Set up other value only when you need to lower
the over-load level.
• The setup value of this parameter is limited by 115[%] of the motor rating.
The over-load protection time characteristics are described on P.6-17.
Pr5.13
Over-speed level setup
Range
Unit
Default
Related
control mode
0 to 20000
r/min
0
P S T F
• If the motor speed exceeds this setup value, Err26.0 Over-speed protection occurs.
• The over-speed level becomes 1.2 times of the motor max. speed by setting up this to 0.
Pr5.14
Motor working range setup
Range
Unit
Default
Related
control mode
0 to 1000
0.1 revolution
10
P S T F
• You can set up the movable range of the motor against the position command input range.
• When the motor movement exceeds the setup value, software limit protection of Err34.0
will be triggered.
Pr5.15
*
I/F reading filter
Range
Unit
Default
Related
control mode
0 to 3
—
0
P S T F
Select reading period of the control input signal.
Setup value
Reading period of the signal.
[0]
0.25 ms
1
0.5 ms
2
1 ms
3
2 ms
Exclude deviation counter clear input (CL) and command pulse inhibit input (INH).
Pr5.16
*
Alarm clear input setup
Range
Unit
Default
Related
control mode
0 to 1
—
0
P S T F
Select alarm clear input (A-CLR) recognition time.
Setup value
Recognition time
[0]
120 ms
1
To Pr5.15 IF reading filter
1. Details of parameter
[Class 5] Enhancing setting
Related page