4-38
Pr3.26
*
Reversal of direction of external scale
Range
Unit
Default
Related
control mode
0 to 3
—
0
P S T F
Reverse the direction of external scale, feedback counter.
Setup value
Content
[0]
Count value of external scale can be used as it is.
1
Sign (positive/negative) of count value of external scale should be inverted.
2 to 3
For manufacturer use
For setting method of this parameter, refer to P.3-12 Full closed control mode.
Pr3.27
*
External scale Z phase disconnection
detection disable
Range
Unit
Default
Related
control mode
0 to 1
—
0
F
Enable/disable Z-phase disconnection detection when A, B phase output type external scale is used.
Setup value
Content
[0]
Valid
1
Invalid
Pr3.28
*
Hybrid deviation excess setup
Range
Unit
Default
Related
control mode
1 to 134217728
Command
unit
16000
F
You can setup the permissible gap (hybrid deviation) between the present motor position
and the present external scale position.
Pr3.29
*
Hybrid deviation clear setup
Range
Unit
Default
Related
control mode
0 to 100
Revolution
0
F
Caution
As the motor turns the number of revolutions set by this parameter, the hybrid deviation is
cleared to 0. No clearing is made with setup value 0.
<Hybrid deviation clear feature>
As the motor reaches the number of revolutions set by Pr3.29 Hybrid deviation clear setup,
clear the hybrid deviation to 0. This feature allows the motor to be used in an application
where hybrid deviation accumulate due to slippage, etc.
Pr3.28
(Hybrid deviation
excess setup)
Pr3.29
(Hybrid deviation clear setup)
Pr3.29
(Hybrid deviation clear setup)
Excess hybrid deviation error
Hybrid deviation value
(command unit) (absolute value)
No. of motor revolutions [rev]
Note: Revolution in the hybrid deviation clear setup is counted by using encoder feedback pulses.
To use the hybrid deviation clear, be sure to set Pr3.29 Hybrid deviation clear setup to the
appropriate value. If the setup value is too small with respect to the value of Pr3.28 Hybrid
deviation excess setup, abnormal operation due to e.g. external scale connection error
cannot be protected.
Limit sensor should be used to assure safety.
1. Details of parameter
[Class 3] Velocity/ Torque/ Full-closed control
Default: [ ]
Note