• A parameter is designated as follows:
Pr0.00 Parameter No.
Class
• For parameters which No. have a suffix of “
*
”
, changed contents will be validated
when you turn on the control power.
• P.3-32... “Inputs and outputs on connector X4”
Default: [ ]
Pr6.30
For manufacturer's use
Range
Unit
Default
Related
control mode
—
—
0
Fixed to 0.
Pr6.31
Real time auto tuning estimation speed
Range
Unit
Default
Related
control mode
0 to 3
—
1
P S T F
Set up the load characteristics estimation speed with the real time auto tuning being valid. A
higher setup value assures faster response to a change in load characteristics but increases
variations in disturbance estimation. Result of estimation is saved to EEPROM every 30
minutes.
Setup value
Mode
Description
0
No change
Stop estimation of load characteristics.
[1]
Almost constant
Response to changes in load characteristics in every minute.
2
Slower change
Response to changes in load characteristics in every second.
3
*
Faster change
Obtain best suitable estimation in response to changes in load
characteristics.
*
If the automatic oscillation detection is enabled by the support software PANATERM, the
setup value 3 is used.
1. Details of parameter
[Class 6] Special setting