4-62
Default: [ ]
Pr5.36
For manufacturer's use
Range
Unit
Default
Related
control mode
—
—
0
Fixed to 0.
Pr5.37
*
Modbus connection setting
Range
Unit
Default
Related
control mode
0 to 2
—
0
P S T F
To set RS232/RS485 communications protocol.
Setup value
Content
[0]
MINAS standard protocol
1
Modbus-RTU (RS232 communications, only for 1:1)
2
Modbus-RTU (RS485 communications, 1:N capable)
Pr5.38
*
Modbus communication setting
Range
Unit
Default
Related
control mode
0 to 5
—
0
P S T F
To set parity (even, odd, none) and stop bit length (1 bit, 2 bit) of Modbus communications.
Setup value
Content
Setup value
Content
[0]
Even/1 bit
3
Odd/2 bit
1
Even/2 bit
4
None/1 bit
2
Odd/1 bit
5
None/2 bit
Pr5.39
Modbus response waiting time
Range
Unit
Default
Related
control mode
0 to 10000
ms
0
P S T F
To set waiting time to be added from the receipt of Modbus communication request till the
transmission of response data.
Note) Delay time will be generated for the creation of response data, even if the value is set
to 0 (zero).
Pr5.40
Modbus communication timeout time
Range
Unit
Default
Related
control mode
0 to 10000
ms
0
P S T F
To set the time required to detect Err. 80.0 “Modbus communication timeout protection” in
case broadcast designated Modbus communications from own specified axis has not been
received exceeding the set time, while maintaining the state where Modbus exercise right is
secured.
Err. 80.0 is not detected when set value is set to 0 (zero).
Pr5.41
For manufacturer’s use
Range
Unit
Default
Related
control mode
—
—
0
Pleses fixed to 0.
1. Details of parameter
[Class 5] Enhancing setting