3-42
Title of
signal
Alarm clear input
Related
control mode
P
S
T
F
Symbol
A-CLR
Default assignment
31 (SI8)
I/F circuit
SI P.3-33
Caution
• Clears the alarm condition.
• This input cannot clear some alarms.
• For details, refer to P.6-3 When in Trouble “Protective function”, P.2-86 “(8) Alarm Display”
and P.7-25 “Display of Battery Alarm”.
When alarm clear input (A-CLR) is kept enabled, all potential alarms and warnings will be
prevented.
Title of
signal
Command pulse inhibition input
Related
control mode
P
S
T
F
Symbol
INH
Default assignment
33 (SI10)
I/F circuit
SI P.3-33
Caution
• Ignores the positional command pulse.
• When using this feature, set Pr5.18 “Invalidation of command pulse inhibition input” to 0.
This function can be assigned to only SI10. Allocation of this function to any other pin will
cause an error.
When INH input is ON, the deviation will be caused between the
positional command
administrated by controller and internal positional command
from the fliter that receives the
positional command from servo drivers, and orginal
location before being input INH positional
command
will be lost. Therefore, it is supposed to reset the orignial location when it needs to
restart return to origin action.
Title of
signal
Control mode switching input
Related
control mode
P
S
T
F
Symbol
C-MODE
Default assignment
32 (SI9)
I/F circuit
SI P.3-33
Caution
• Selects a control mode.
• This signal is required in all control modes. No setting will cause an error.
• Do not input any command 10 ms before and after changing the control mode.
Title of
signal
Electronic gear (division/multiplication) switching input 1
Related
control mode
P
S
T
F
Symbol
DIV1
Default assignment
28 (SI5)
I/F circuit
SI P.3-33
Title of
signal
Electronic gear (division/multiplication) switching input 2
Related
control mode
P
S
T
F
Symbol
DIV2
Default assignment
—
I/F circuit
SI P.3-33
• Up to 4 numerators can be used for command dividing/multiplying by using DIV1 and DIV2.
<DIV1 and DIV2 vs numerator/denominator of selected command dividing/multiplying process>
DIV1
DIV2
Selected command dividing/multiplying process
Numerator
Denominator
OFF
OFF
Pr0.09
Pr0.10
ON
OFF
Pr5.00
Pr0.10
OFF
ON
Pr5.01
Pr0.10
ON
ON
Pr5.02
Pr0.10
The numerator of command division can be changed by using DIV1 and DIV2 can be
switched
, the relationship of the
positional command that send from servo drivers and internal
positional command
will be change. Therefore, it is supposed to reset the orignial location
when it needs to restart return to origin action.
4. Inputs and outputs on connector X4
Input Signal and Pin No.