4-42
Default: [ ]
Pr4.16
Type of analog monitor 1
Range
Unit
Default
Related
control mode
0 to 28
—
0
P S T F
Select the type of monitor for analog monitor 1.
*
See the table shown on the next page.
Pr4.17
Analog monitor 1 output gain
Range
Unit
Default
Related
control mode
0 to 214748364
[Monitor unit
in Pr4.16] / V
0
P S T F
Set up the output gain of analog monitor 1.
For Pr4.16 = 0 Motor speed, 1 V is output at the motor speed [r/min] = Pr4.17 setup value.
Pr4.18
Type of analog monitor 2
Range
Unit
Default
Related
control mode
0 to 28
—
4
P S T F
Select the type of monitor for analog monitor 2.
*
See the table shown on the next page.
Pr4.19
Analog monitor 2 output gain
Range
Unit
Default
Related
control mode
0 to 214748364
[Monitor unit
in Pr4.16] / V
0
P S T F
Set up the output gain of analog monitor 2.
For Pr4.18 = 4 Torque command, 1 V is output at the torque command [%] = Pr4.19 setup value.
Pr4.20
For manufacturer's use
Range
Unit
Default
Related
control mode
—
—
0
Plese fixed to 0.
Pr4.16/Pr4.18
Type of monitor
Unit
Output gain for setting
Pr4.17/Pr4.19 = 0
0
Motor speed
r/min
500
1
Positional command speed
*
4
r/min
500
2
Internal positional command speed
*
4
r/min
500
3
Velocity control command
r/min
500
4
Torque command
%
33
5
Command positional deviation
*
5
pulse (Command unit)
3000
6
Encoder positional deviation
*
5
pulse (Encoder unit)
3000
7
Full-closed deviation
*
5
pulse (External scale unit)
3000
8
Hybrid deviation
pulse (Command unit)
3000
9
Voltage across PN
V
80
10
Regenerative load factor
%
33
11
Overload factor
%
33
12
Positive direction torque limit
%
33
13
Negative direction torque limit
%
33
14
Speed limit value
r/min
500
15
Inertia ratio
%
500
16
Analog input 1
*
2
V
1
1. Details of parameter
[Class 4] I/F monitor setting