• A parameter is designated as follows:
Pr0.00 Parameter No.
Class
• For parameters which No. have a suffix of “
*
”
, changed contents will be validated
when you turn on the control power.
• P.3-32... “Inputs and outputs on connector X4”
Default: [ ]
Pr2.24
5th notch frequency
Range
Unit
Default
Related
control mode
50 to 5000
Hz
5000
P S T F
Caution
Set the center frequency of the 5th notch filter.
The notch filter function will be invalidated by setting up this parameter to "5000".
Pr2.25
5th notch width selection
Range
Unit
Default
Related
control mode
0 to 20
—
2
P S T F
Caution
Set the width of notch at the center frequency of the 5th notch filter.
Higher the setup, larger the notch width you can obtain. Use with default setup in normal
operation.
Pr2.26
5th notch depth selection
Range
Unit
Default
Related
control mode
0 to 99
—
0
P S T F
Caution
Set the depth of notch at the center frequency of the 5th notch filter.
Higher the setup, shallower the notch depth and smaller the phase delay you can obtain.
Pr2.27
1st vibration control width setting
Range
Unit
Default
Related
control mode
0 to 1000
—
0
P
F
To conduct fine tuning of 1st vibration suppression control function.
Pr2.28
2nd vibration control width setting
Range
Unit
Default
Related
control mode
0 to 1000
—
0
P
F
To conduct fine tuning of 2nd vibration suppression control function.
Pr2.29
3rd vibration control width setting
Range
Unit
Default
Related
control mode
0 to 1000
—
0
P
F
To conduct fine tuning of 3rd vibration suppression control function.
Pr2.30
4th vibration control width setting
Range
Unit
Default
Related
control mode
0 to 1000
—
0
P
F
To conduct fine tuning of 4th vibration suppression control function.
1. Details of parameter