• A parameter is designated as follows:
Pr0.00 Parameter No.
Class
• For parameters which No. have a suffix of “
*
”
, changed contents will be validated when
you turn on the control power.
• P.3-32... “Inputs and outputs on connector X4”
Default: [ ]
Pr6.22
*
A, B phase external scale pulse output
method selection
Range
Unit
Default
Related
control mode
0 to 1
—
0
F
Select the pulse regeneration method of A, B and Z parallel external scale.
Setup value
Regenerating method
[0]
Directly output the signals from A, B and Z parallel external scales.
1
Output A and B phase signals recovered from A, B and Z parallel external scales.
Z-phase is output directly.
Pr6.23
Load fluctuation compensating gain
Range
Unit
Default
Related
control mode
−100 to 100
%
0
P S
F
Sets the compensation gain for the load fluctuation.
Pr6.24
Load fluctuation compensating filter
Range
Unit
Default
Related
control mode
10 to 2500
0.01 ms
53
P S
F
Sets the filter time constant for the load fluctuation.
Pr6.27
*
Alarm latch time selection
Range
Unit
Default
Related
control mode
0 to 10
—
5
P S T F
Set up the latch time.
Setup value
Content
0
Latch time: infinite
1
Latch time
1 [s]
2
2 [s]
3
3 [s]
4
4 [s]
[5]
5 [s]
6
6 [s]
7
7 [s]
8
8 [s]
9
9 [s]
10
10 [s]
Pr6.28
*
Special function selection
Range
Unit
Default
Related
control mode
0 to 1
—
0
P
Selects between enabling and disabling the block operation function.
Setup value
Writing
[0]
Block operation disabled
1
Block operation enabled
1. Details of parameter
[Class 6] Special setting