4-60
Default: [ ]
Pr5.28
*
LED initial status
Range
Unit
Default
Related
control mode
0 to 42
—
1
P S T F
Power -ON
Setup value
of Pr5.28
Flashes (for approx. 2 sec) during initialization
Setup
value
Content
Setup
value
Content
Setup
value
Content
0
Positional command deviation
14
Regenerative load factor
28
Software version
[1] Motor speed
15
Over-load factor
29
Driver serial number
2
Positional command speed
16 Inertia ratio
30 Motor serial number
3
Velocity control command
17 Factor of no-motor running
31
Accumulated operation time
4
Torque command
18
No. of changes in I/O signals
32
Automatic motor recognizing function
5
Feedback pulse sum
20
Absolute encoder data
33 Temperature information
6
Command pulse sum
21
Absolute external scale position
35 Safety condition monitor
8
External scale feedback pulse sum
22
No. of encoder communication errors monitor
38
Motor power
9
Control mode
23
Communication axis address
39 For manufacturer use
10 I/O signal status
24
Encoder positional deviation [Encoder unit]
40 For manufacturer use
11
Analog input value
25
External scale deviation [External scale unit]
41
For manufacturer use
12 Error factor and reference of history 26
Hybrid deviation [Command unit]
42
For manufacturer use
13
Alarm Display
27
Voltage across PN [V]
You can select the type of data to be displayed on the front panel LED (7 segment) at the
initial status after power-on.
For details of display, refer to P.2-88 "How to Use the Front Panel" of Preparation.
Pr5.29
*
Baud rate setup of
RS232 communication
Range
Unit
Default
Related
control mode
0 to 7
—
2
P S T F
Note
You can set up the communication speed of RS232.
For baud rate setup value, refer to RS485 setup.
Pr5.30
*
Baud rate setup of
RS485 communication
Range
Unit
Default
Related
control mode
0 to 7
—
2
P S T F
You can set up the communication speed of RS485.
Setup value
Baud rate
Setup value
Baud rate
0
2400 bps
4
38400 bps
1
4800 bps
5
57600 bps
[2]
9600 bps
6
115200 bps
3
19200 bps
7
230400 bps
Baud rate error is ±0.5 % for 2400 to 38400 bps, and ±2 % for 57600 to 115200 bps.
*When not modbus communication (Pr5.37=0),if the set value is 7,the internal is 9600bps.
1. Details of parameter
[Class 5] Enhancing setting