Default: [ ]
1. Details of parameter
[Class 2] Damping control
Pr2.12
4th notch depth selection
Range
Unit
Default
Related
control mode
0 to 99
—
0
P S T F
Caution
Set the depth of notch at the center frequency of the 4th notch filter.
Higher the setup, shallower the notch depth and smaller the phase delay you can obtain.
When the applicable filter function is used, parameter value is automatically set.
Pr2.13
Selection of damping filter switching
Range
Unit
Default
Related
control mode
0 to 6
—
0
P
F
Among 4 filters select the filters to be used for damping control.
• When setup value is 0: Up to 2 filters can be used simultaneously.
• When setup value is 1 or 2: Select the filter with external input(s) (VS-SEL1 and/or VS-SEL2).
Setup
value
VS-SEL2
VS-SEL1
1st damping 2nd damping 3rd damping 4th damping
[0]
—
—
1
—
OFF
—
ON
2
OFF
OFF
OFF
ON
ON
OFF
ON
ON
• With setup value 3: Select the filter with command direction.
Setup
value
Position command
direction
1st damping 2nd damping 3rd damping 4th damping
3
Positive direction
Negative direction
Contents of setup values 4 to 6 will differ with enabled/disabled switching of two degree-of-
freedom control mode.
• Position control (Two degree-of-freedom control mode disabled).
Setup value
VS-SEL1
1st model
2nd model
3st model
4st model
4
—
○
○
○
5,6
Same action as set value 0
• Position control (Two degree-of-freedom control mode enabled).
Setup value
VS-SEL1
1st model
2nd model
4
—
○
○
5
OFF
○
ON
○
Setup value
Position command direction
1st model
2nd model
6
Positive direction
○
Negative direction
○
• full-close control .
Setup value
1st model
2nd model
3st model
4st model
4 to 6
○
○
Caution
• Switching of damping controls will be done on the rising edge of the command whose number of
pulses/0.125 ms has been changed from 0 while the positioning complete signal is being output.
When the damping frequency is increased or disabled, and positioning complete range is large, and
pulses are stored in the filter at that time (the area represented by the value of position command before
filter subtracted by the value of position command after filter and integrated with the time). Note that since
these pulses will be discharged at a higher rate upon switching to return back to the original position, the
motor may run at a speed higher than the command speed for a short time.