Protective
function
Error code No.
Causes
Measures
Main Sub
6-10
1. When in Trouble
Protective function (Detail of error code)
*
I/F input
function
number error 2
33
3
Input signals (SI6, SI7, SI8, SI9, SI10)
are assigned with undefined number.
Allocate correct function to each connector
pin.
*
I/F output
function
number error 1
4
Output signals (SO1, SO2, SO3) are
assigned with undefined number.
*
I/F output
function
number error 2
5
Output signals (SO4, SO5, SO6) are
assigned with undefined number.
*
Counter clear
allocation
error
6
Counter clear function is assigned to a
signal number other than SI7.
*
Command
pulse
inhibition input
allocation error
7
Command pulse inhibit input function is
assigned to a signal number other than
SI10.
Motor
working range
setup error
protection
34
0
The motor has exceeded the motor
working range set to Pr5.14 “Allowable
motor operating range setting” against
the position command input range.
1) Gain is not appropriate.
2) Pr5.14 setup value is low.
1) Check the gain (balance between position
loop gain and speed loop gain) and inertia
ratio.
2) Increase the setup value of Pr5.14. Or,
Set Pr5.14 to 0 to disable the protective
function.
*
EEPROM
parameter
error
protection
36
0
Data in parameter storage area has been
damaged when reading the data from
EEPROM at power-on.
• Set up all parameters again.
• If the error persists, replace the driver (it
may be a failure.) Return the product to the
dealer or manufacturer.
1
*
EEPROM
check code
error
protection
37
0
Data for writing confirmation to EEPROM
has been damaged when reading the
data from EEPROM at power-on.
Replace the driver. (it may be a failure).
Return the product to a dealer or
manufacturer.
1
2
*
Drive
prohibition
input
protection
38
0
Both positive and negative direction drive
prohibition inputs (POT and NOT) have
been turned ON at Pr5.04 “Over-travel
inhibition input setting” =0.
Either positive direction drive prohibition
input or negative direction drive
prohibition input has been turned ON at
Pr5.04=2.
• Check that there is no error in the switches,
wires and power supply connected to the
positive direction/negative direction drive
prohibition input. Check particularly that
start-up of the power supply for the control
signal (DC12 to 24 V) is not slow.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]