GENESIS (Model LT3140) – Technical Manual

 

GENERAL DESCRIPTION

 

The Genesis, model LT3140 is Bartlett Instrument’s 8

th 

generation kiln controller. We’ve 

enhanced all the great features from older models and added many new ones. The Genesis kiln controller 
regulates the temperatures in a kiln according to the program set by the artist. It has two different 
programming modes, Novice Mode and Advanced Programming. It can control a single zone or multi-
zone kiln.  

 

POWER SUPPLY

 

The LT3140 board requires a 24V center-tap transformer, as did its predecessors. It connects to 

the board’s bottom three quick connects, labeled AC1, CENTER TAP, and AC2. The VA rating of the 
transformer is dependent on the electrical load of the board and relays. The board requires approximately 
80mA at 12V DC and a relay typically requires approximately 140mA at 12V DC. Therefore, a three-
relay system will require a transformer with a minimum rating of 6VA (500mA X 12V DC = 6 VA).  

 

OUTPUTS

 

The LT3140 board has five 12V DC outputs. Four outputs are given power by a safety transistor, 

outputs 1, 2, 3, and safety. The safety transistor is capacitor coupled to the microprocessor so it only 
powers the output transistors when the microprocessor is operating correctly. Outputs 1, 2, and 3 respond 
to their respective thermocouple inputs. All outputs are capable of driving a 500mA 12 V DC load. 
Output 4 is an extra output that can be programmed to run a fan, alarm, or extra kiln section. The 
maximum combined output of all outputs is 1 Amp. The safety output powers on at the beginning of a 
firing and off at the end of the firing. It is used to drive a safety relay that sends line power to the 
switching relays on outputs 1, 2, and 3. When using the optional current sensor, wiring one section to 
each output will give an Amp reading per section for better diagnostics. See Configuration in the 
controllers Menu for details on the output 4 options.  

 

FACTORY CONFIGURATION - “HIDDEN MENU”

 

The “hidden” menu allows programming of options that are normally set at the factory. The 

options are listed in the order they appear in the menu with a description. The “hidden” menu can be 
entered by pressing “MENU”, scroll down to “Factory Configuration”, and selecting “Factory 
Configuration. Then, type in the sequence 4, 4, 3, and the Factory Configuration options will be 
displayed. Use the scroll bar on the right to scroll through the options found below: 

TC Type, Max 

Program Temperature, Max Board Temperature, SSR Mode, Cycle Time, Current Sensor Rating, 

and 

Run Factory Diag. 

 

 
TC Type 

 

Change the thermocouple type used with the controller from Type K, Type S, or Type R. To 

change thermocouple type in Factory Configuration, select the thermocouple type being used with the 
controller and press “

Save

”. When changing from a Type K to a Type S or Type R, you must change the 

software setting as well as placing a jumper on the circuit board. To change from a Type S or Type R to a 
Type K requires changing the software setting and removing a jumper from the circuit board.  

 

WARNING: 

Using a Type S thermocouple and a controller set for Type K will cause serious 

over-fire. Using a Type K thermocouple and a controller set for Type S will cause an under-fire. Type S 
thermocouples must use Type S extension wire. Type K thermocouples must use Type K extension wire. 
If changing thermocouple type be sure to change the extension wire. Make sure the software and jumper 
settings match the type of thermocouple and extension wire you are using.  