4-1
Section
Overall Structure
58
C200HW-NC213
I/O
Word address
Axis
Output
I to I+5
Common
p
I+6 to I+10
X axis
I+11 to I+15
Y axis
Input
I+16 to I+17
X axis
p
I+18 to I+19
Y axis
C200HW-NC413
I/O
Word address
Axis
Output
I to I+5
Common
p
I+6 to I+10
X axis
I+11 to I+15
Y axis
I+16 to I+20
Z axis
I+21 to I+25
U axis
Input
I+26 to I+27
X axis
p
I+28 to I+29
Y axis
I+30 to I+31
Z axis
I+32 to I+33
U axis
Note
“I” represents the beginning word address of the area designated by the com-
mon parameter area.
Example
0
m
15
00
Common Parameter Area
0
0
D
0
m+1
1
0
0
When the common parameter area settings are made as shown in this example,
the operating data area will be allocated to DM 0100 onwards.
There is no EM area for C200H/HS/HE Programmable Controllers, so in that
case the EM area cannot be designated for the operating data area.
For details regarding data transfer area settings, refer to
Operating Data Area
under
4-1-4 Data Areas
.
4-1-4 Data Areas
Parameter Area
Common Parameters (Data Memory)
Designation of Operating Data Area
Word m
0
15
00
0
0
X
Designate the memory area to which the operating memory is to be set.
X = D (DM area)
E (EM area)
Beginning Word of Operating Data Area
Word m+1
x10
3
15
00
x10
2
x10
1
x10
0
Data Transfer Area
Содержание C200HW
Страница 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Страница 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 233: ...10 7 Section Transferring and Saving Data 224 Setting of operating data area for reading data READ DATA ...
Страница 284: ...Cat No W334 E1 04 Note Specifications subject to change without notice Printed in Japan Authorized Distributor ...
Страница 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...