![Omron C200HW Скачать руководство пользователя страница 209](http://html1.mh-extra.com/html/omron/c200hw/c200hw_operation-manual_742329209.webp)
10-2
Section
Memory Operation
200
Program
Operation start
switch
Busy Flag
Sets #0 for the
sequence number.
Sequence
number enable
Enables the
sequence number.
START
No Origin
Flag
Takes the rising edge of the
operation start switch.
Only executed when
starting the first
time.
Executed when
starting from the
second time
onwards.
No Origin Flag
Busy Flag
10-2-3 Cancelling Positioning
Overview
•
A forced interrupt can be used during memory operation to cancel the current
positioning and perform a circumvention in case of an emergency.
•
This operation forcibly cancels the current positioning operation and executes
positioning from the designated sequence number.
•
The pulses currently being output are stopped immediately without decelera-
tion.
Содержание C200HW
Страница 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Страница 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 233: ...10 7 Section Transferring and Saving Data 224 Setting of operating data area for reading data READ DATA ...
Страница 284: ...Cat No W334 E1 04 Note Specifications subject to change without notice Printed in Japan Authorized Distributor ...
Страница 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...