4-3
Section
Axis Parameters
81
Deceleration Time (Rightmost Word)
X axis m+17 (NC113), Y axis m+41 (NC213), Z axis m+65 and U axis m+89 (NC413)
Deceleration Time (Leftmost Word)
X axis m+18 (NC113), Y axis m+42 (NC213), Z axis m+66 and U axis m+90 (NC413)
15
00
0
0
x10
5
x10
4
x10
3
x10
2
x10
1
x10
0
Leftmost word
00
15
Rightmost word
This setting specifies the time from the maximum speed until 0 pps or initial
speed is reached.
•
Range: 0 to 250,000 (ms)
Positioning Monitor Time
X axis m+19 (NC113), Y axis m+43 (NC213), Z axis m+67 and U axis m+91 (NC413)
15
00
x10
3
x10
2
x10
1
x10
0
After pulse output has been completed, a positioning timer timeout error (error
code 8600) will be generated if the positioning completed signal does not turn
ON within the time set here. (This function is only enabled for operation modes 2
and 3.)
•
Range: 0 to 9,999 (ms)
If the positioning monitor time is set to “0,” the positioning completed signal will
be awaited only when an origin search operation is executed. For all other
operations (such as jogging, memory operation, and so on), the positioning
completed signal will be ignored.
CCW Limit (Rightmost Word)
X axis m+20 (NC113), Y axis m+44 (NC213), Z axis m+68 and U axis m+92 (NC413)
CCW Limit (Leftmost Word)
X axis m+21 (NC113), Y axis m+45 (NC213), Z axis m+69 and U axis m+93 (NC413)
CW Limit (Rightmost Word)
X axis m+22 (NC113), Y axis m+46 (NC213), Z axis m+70 and U axis m+94 (NC413)
CW Limit (Leftmost Word)
X axis m+23 (NC113), Y axis m+47 (NC213), Z axis m+71 and U axis m+95 (NC413)
15
00
Sign
x10
6
x10
5
x10
4
x10
3
x10
2
x10
1
x10
0
Leftmost word
00
15
Rightmost word
These settings specify the CCW and CW software limits.
•
Sign:
0: Positive (CW); 1: Negative (CCW)
•
Range: –9,999,999 to 9,999,999 (ms)
If the CW software limit is set to less than or equal to the CCW limit, the software
limit will not function. When this setting is made, operation proceeds as follows:
•
At the beginning of operation, the present position is always 0.
•
During axis operation the present position is always refreshed, and if the upper
or lower limit is reached positioning will be stopped.
Upper Limit: +9,999,999 (pulses)
Lower Limit: –9,999,999 (pulses)
Reserved
X axis m+24, m+27 (NC113), Y axis m+48, m+51 (NC213), Z axis m+72, m+75 and U axis m+96, m+99
(NC413)
Set to 0000.
Содержание C200HW
Страница 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Страница 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 233: ...10 7 Section Transferring and Saving Data 224 Setting of operating data area for reading data READ DATA ...
Страница 284: ...Cat No W334 E1 04 Note Specifications subject to change without notice Printed in Japan Authorized Distributor ...
Страница 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...