![Omron C200HW Скачать руководство пользователя страница 239](http://html1.mh-extra.com/html/omron/c200hw/c200hw_operation-manual_742329239.webp)
11-2
Section
LED Error Indicators
230
11-2 LED Error Indicators
The status of the LED indicators on the front of the Position Control Unit can be
used to diagnose errors as shown in the following table. The status of the indica-
tors is as follows:
f
: ON
l
: Flashing
F
: OFF
(For the “data error” and “external sensor input,” the corresponding axis will be
flashing.)
C200HW-NC413
C200HW-NC213
C200HW-NC113
LED
Error
Cause
Remedy
R
U
N
E
R
R
S
E
N
S
D
A
T
A
X
Y
Z
U
y
F F F F F F F F
PC power supply
OFF
The PC’s power supply is off.
Turn on the PC’s power
supply.
Not mounted to
Backplane
The Unit isn’t mounted
securely to the PC
Backplane.
Mount the Unit to the
Backplane securely.
CPU standby
One of the Special I/O Units
is faulty.
The faulty Unit will be
indicated with a “$
**
”
character when the I/O Table
Read operation is performed.
Replace the faulty Unit.
I/O Unit over
The same unit number has
been set on two Special I/O
Units or an invalid unit
number has been set.
Change the unit number
settings to eliminate any
duplication or invalid
settings.
I/O Bus error
The PCU or I/O Connecting
Cable isn’t connected
correctly.
Check to be sure that the
PCU is correctly mounted to
the Backplane. Check the I/O
Connecting Cables to each
Rack.
CPU Bus Unit error
Refreshing with the PC
couldn’t be performed
correctly.
The Position Control Unit is
mounted to a Slave Rack,
but the parameter
designation is set to “00.”
After eliminating the cause of
the error, restart the Unit with
the corresponding Restart Bit
in the SR or AR area.
Set the designation to “01”
and restart the Unit.
I/O setting error
An I/O table verification error
occurred.
Register the I/O table again.
If the error recurs, replace
the Unit.
F f f f
–
–
–
–
Internal component
faulty
A component within the
Position Control Unit failed.
Restart the Unit by turning
the power on again or
toggling the corresponding
Restart Bit. If the error
recurs, replace the Unit.
f F F F
–
–
–
–
Normal operation
---
---
f f F F
–
–
–
–
Error occurred
An error other than a data
error occurred during
external sensor input.
Check the error code and
correct the error.
Содержание C200HW
Страница 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Страница 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 233: ...10 7 Section Transferring and Saving Data 224 Setting of operating data area for reading data READ DATA ...
Страница 284: ...Cat No W334 E1 04 Note Specifications subject to change without notice Printed in Japan Authorized Distributor ...
Страница 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...