![Omron C200HW Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/omron/c200hw/c200hw_operation-manual_742329018.webp)
1-2
Section
System Configuration
5
•
There are restrictions on the maximum current provided to each Rack and the
the current consumption for each Unit. For details, refer to the appropriate Pro-
grammable Controller operation manual.
•
There are restrictions on the use of Remote I/O Slave Racks. These restric-
tions are explained in
Restrictions on Using Remote I/O Slave Racks
below.
As shown in the following table, the number of Special I/O Units that can be used
on a single Remote I/O Slave Rack is determined by the the particular Special
I/O Unit group (A, B, C, or D).
Group A
Group B
Group C
Group D
Units in
group
High-speed Counter
Units
Position Control Unit
(NC111/112)
(NC113/213)
ASCII Units
Analog I/O Units
ID Sensor Units
Fuzzy Logic Units
High-density I/O Units
Temperature Control
Units
Heat/Cool Temperature
Control Units
PID Control Units
Cam Positioner Unit
Temperature Sensor Units
Voice Unit
Position Control Units
(NC211)
(NC413)
Number of
Units that
can be used
4 Units
8 Units
6 Units
2 Units
•
If Special I/O Units from different groups are to be mixed, then use a combina-
tion that satisfies the following two formulas:
3A + B + 2C + 6D
x
12
A + B + C + D
x
8
•
There are restrictions on the number of Units that can be used with particular
CPU Units. For details, refer to
Number of Usable Units
described previously.
System Configuration Considerations
•
The I/O bits allocated to a particular Special I/O Unit are determined by the unit
number that is set by the switch on the front panel of the Unit, and not by the slot
in which the Unit is mounted.
•
With the C200H, do not mount a Position Control Unit in the two slots adjacent
to the CPU Unit. If it is mounted in those slots, it will not be possible to mount
tools such as the Programming Console.
•
Special I/O Units cannot be used with C200H Remote I/O Slave Racks that are
connected to Remote I/O Master Racks for other SYSMAC Programmable
Controller models (such as C120, C500, C1000H, and C2000H).
Follow the procedure outlined below to mount the Position Control Unit to the
Backplane.
1, 2, 3...
1. Insert the hook on the upper rear of the Unit into the slot in the Backplane.
Hook
Backplane
Lock lever
2. Carefully insert the Unit into the connector on the Backplane.
Restrictions on Using
Remote I/O Slave Racks
Mounting the Unit
Содержание C200HW
Страница 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Страница 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 233: ...10 7 Section Transferring and Saving Data 224 Setting of operating data area for reading data READ DATA ...
Страница 284: ...Cat No W334 E1 04 Note Specifications subject to change without notice Printed in Japan Authorized Distributor ...
Страница 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...