background image

 

 
 

 

 

 

 

053-060 
ISSUE 1 

D E E P   S E A   E L E C T R O N I C S  

 

 

DSE6120 Installation Instructions

 

 

 
ACCESSING THE FRONT PANEL EDITOR (FPE) 

 
 

The module must be in STOP mode with the engine at rest before configuration mode can be accessed. 

To enter the ‘configuration mode’ press both the INFO 

and STOP 

buttons together.

 

 

ENTERING THE CONFIGURATION EDITOR PIN NUMBER 

 

If the module PIN number has been set, the PIN number request is then shown. The configuration 
cannot be viewed or changed until the PIN number is correctly entered.  
 

 

The first * is flashing. Press + or – buttons to adjust  it to the correct value for the first digit of 
the PIN number.  

 

Press 

 when the first digit is correctly entered.  

 

The entered digit will turn back to a * to maintain security.  

 

Enter the remaining digits of the pin number using the same method. 

 

 
If the Configuration PIN has been entered successfully (or the PIN number has not been set in the module) the first 
configurable parameter is displayed. 
 

NOTE:-  When 

 is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not 

correct, the editor is automatically exited. To retry you must re-enter the editor as described above

 

 

EDITING A PARAMETER 

 

Enter the editor as described above.  
 

 

Press 

 to select the required ‘page’ as detailed below. 

 

Press  

 (+)  to select the next parameter or  

 (-) to select the previous parameter within the current page. 

 

When viewing the parameter to be changed, press the 

 (

) button. The value begins to flash.  

 

Press

 (+) or 

  (-) to adjust the value to the required setting. 

 

Press 

 (

)  the save the current value, the value ceases flashing. 

 

Press and hold the 

 (

)  button to exit the editor. 

NOTE: - 

Values representing pressure will be displayed in Bar.  Values representing temperature are displayed in 

degrees Celsius

.  

 

NOTE: - When the editor is visible, it is exited after 5 minutes of inactivity to ensure security.

 

 

NOTE:- To exit the front panel configuration editor at any time, press and hold the 

 (

)  button. Ensure you 

have saved any changes you have made by pressing the 

 button first. 

 

NOTE:-  The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure 

security. 

 

 

 

Deep Sea Electronics Plc. 

Tel:+44 (0)1723 890099 

Fax: +44 (0)1723 893303 

LO CALL (from UK BT landlines)  

Telephone 0845 260 8933 

Email: [email protected]  

Web: www.deepseaplc.com 

Deep Sea Electronics inc. 

Phone: +1 (815) 316-8706 

Fax: +1 (815) 316- 8708 

TOLL FREE (USA only) : 

Tel: 1 866 636 9703  

Email: [email protected] 

Web: www.deepseausa.com 

 

Deep Sea Electronics Plc. 

(Far East) 

Tel:+66 2 670 6228 

Fax: +66 2 678 3028 

 

Email: [email protected] 

Web: www.deepseaplc.com 

 

Typical Wiring Diagram 

 

Reviews: