APPENDIX
App. - 43
2)
3)
4)
1)
App. 8 Analog monitor
POINT
A voltage of analog monitor output may be irregular at power-on.
The servo status can be output to two channels in terms of voltage.
(1) Setting
Change the following digits of [Pr. PC09] and [Pr. PC10].
Analog monitor 1 output selection
(the signal provided to the output across MO1 and LG)
0 0
[Pr. PC09]
Analog monitor 2 output selection
(the signal provided to the output across MO2 and LG)
0 0
[Pr. PC10]
[Pr. PC11] and [Pr. PC12] can be used to set the offset voltages to the analog output voltages. Setting
value is -999 mV to 999 mV.
Parameter
Description
Setting range [mV]
PC11
This is used to set the offset voltage of MO1 (Analog monitor 1).
-999 to 999
PC12
This is used to set the offset voltage of MO2 (Analog monitor 2).