5. PARAMETERS
5 - 45
No./
symbol/name
Setting
digit
Function
Initial
value
[unit]
Network
ECT EIP
PC20
*COP7
Function
selection C-7
_ _ _ x [AL. 10 Undervoltage] detection method selection
Set this parameter when [AL. 10 undervoltage] occurs due to distorted power supply
voltage waveform while using FR-RC-(H) or FR-CV-(H).
0: [AL. 10] not occurrence
1: [AL. 10] occurrence
0h
_ _ x _ For manufacturer setting
0h
_ x _ _ Undervoltage alarm selection
Select the alarm and warning that occurs when the bus voltage drops to the
undervoltage alarm level.
0: [AL. 10] regardless of servo motor speed
1: [AL. E9] at servo motor speed 50 r/min (50 mm/s) or less, [AL. 10] at over 50 r/min
(50 mm/s)
0h
x _ _ _ For manufacturer setting
0h
PC21
*BPS
Alarm history
clear
_ _ _ x Alarm history clear selection
This parameter is used to clear the alarm history.
0: Disabled
1: Enabled
When "Enabled" is set, the alarm history will be cleared at the next power-on. After
the alarm history is cleared, the setting is automatically disabled.
0h
_ _ x _ For manufacturer setting
0h
_ x _ _
0h
x _ _ _
0h