15. USING A DIRECT DRIVE MOTOR
15 - 13
(5) Setting of the magnetic pole detection voltage level by the position detection method
For the magnetic pole detection by the position detection method, set the voltage level with [Pr. PL09
Magnetic pole detection voltage level]. For the magnetic pole detection by the minute position detection
method, the voltage level setting is not required.
(a) Guideline of parameter settings
Set the parameters by referring to the following table.
[Pr. PL09] setting
(Guide value)
Servo status
Small
←
Medium
→
Large
(10 or less (initial value) 50 or more)
Torques required for operation
Small
Large
Overload, overcurrent alarm
Not frequently occurs
Frequently occurs
Magnetic pole detection alarm
Frequently occurs
Not frequently occurs
Magnetic pole detection accuracy
Low
High
(b) Setting procedure
1) Perform the magnetic pole detection, and increase the setting value of [Pr. PL09 Magnetic pole
detection voltage level] until [AL. 50 Overload 1], [AL. 51 Overload 2], [AL. E1 Overload warning
1], and [AL. EC Overload warning 2] occur. Increase the setting value by five as a guide value.
When these alarms and warnings occur during the magnetic pole detection by using MR
Configurator2, the test operation of MR Configurator2 automatically completes and the servo-off
status is established.
2) Specify the setting value that is an approximately 70% of the value set when [AL. 50 Overload 1],
[AL. 51 Overload 2], [AL. E1 Overload warning 1], and [AL. EC Overload warning 2] occurred as
the final setting value. However, if [AL. 27 Initial magnetic pole detection error] occurs with this
value, specify a value intermediate between the value set at [AL. 50 Overload 1], [AL. 51
Overload 2], [AL. E1 Overload warning 1], or [AL. EC Overload warning 2] and the value set at
the magnetic pole detection alarm as the final setting value.
3) Perform the magnetic pole detection again with the final setting value.
(c) Setting example
Existent
Non-existent
Alarm
Magnetic pole detection
[Pr. PL09] setting value
An alarm has occurred when the setting
value of [Pr. PL09] is set to 70.
While increasing the setting value of [Pr. PL09], carry out the
magnetic pole detection repeatedly.
30
35
40
45
65
70
In this example, the final setting value of [Pr. PL09] is 49 (Setting value at the alarm occurrence = 70
× 0.7).
Содержание MR-J4 TM Series
Страница 9: ...A 8 MEMO ...
Страница 17: ...8 MEMO ...
Страница 225: ...5 PARAMETERS 5 86 MEMO ...
Страница 295: ...8 TROUBLESHOOTING 8 14 MEMO ...
Страница 439: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 6 MEMO ...
Страница 521: ...16 FULLY CLOSED LOOP SYSTEM 16 20 MEMO ...
Страница 578: ...APPENDIX App 41 ...